EN/JP

PRODUCT RESERCH

Mica tape for coil insulation

Details

We provide mica tape that features good windability with coils of generators, rotary machines, and electric motors, and is used for insulation systems for high-voltage coils.

Features

  • (1) Dry mica tape has great impregnating ability.
  • (2) Prepreg mica tape is made only by heat pressing and can be integrally molded.
  • (3) It has great windability to adhere to coils because of its good flexibility and excellent wrapping ability.
  • (4) Including corona resistance, it provides excellent electric insulation.
  • (5) It has excellent heat resistance and may be used even for high heat resistance classes (former class F, class H, etc.).

Usages

  • (1) Insulation for various types of high-voltage coils, such as those used in generators, electric motors, rotary machines, etc.
  • (2) Insulation between slot cells and coils.
  • (3) Insulation between layers of high-voltage equipment.

Composition and standard dimensions of the dry mica tape

DL86-VD5 DL86-4C DG86-TD1
Mica Mica paper based on uncalcined muscovite
Binder Epoxy resin
Reinforcement material Polyester film (0.025 mm thick) Glass cloth
Standard dimensions Thickness (mm) 0.065 0.13 0.13/0.18
Width (mm) 7<
Length (m) 600<

Properties of dry mica tape

DL86-VD5 DL86-4C DG86-TD1
Product weight g/m2 100 200 190
Mica contents % 60 80 85
Binder contents % 6 5 5
Tensile strength N/15 wide 70 70 100
Dielectric breakdown voltage kV 8 8 2

*Measurement methods were complied with JIS C 2116.
*The above values are examples from tests, and are not guaranteed values.

Composition and standard dimensions of the prepreg mica tape

DG86-TP1
Mica Mica paper based on muscovite
Binder Epoxy
Reinforcement material Glass cloth
Standard dimensions Thickness (mm) 0.18
Width (mm) 10 or more
Length (m) 30 or 50 (Please consult us)

Properties of prepreg mica tape

DG86-TP1
Nominal thickness mm 0.18
Tensile strength N/10 mm
wide
89
Binder contents wt% 50 or less
Dielectric breakdown voltage kV 6.0

*Measurement methods were complied with JIS C 2116.
*The above values are examples from tests, and are not guaranteed values.